Condensation on AC Vents — Causes, Fixes, and When to Worry

"Every morning I find water droplets on my ceiling vents and there are brown water stains forming on the ceiling around the registers. Is my AC leaking or is this something else?"

If you've walked into a room and noticed water dripping from your AC vent — or found a damp ring of discoloration spreading across the ceiling around a supply register — your first instinct is probably that your air conditioner is leaking. It almost certainly isn't.

What you're seeing is condensation. The cold metal surface of your supply vent has dropped below the dew point of the surrounding room air, and moisture is condensing directly onto the grille — exactly like water beading on a cold glass of iced tea on a humid summer day.

Here's the reassuring part: this is almost always a humidity problem, not a system failure. In the vast majority of cases, high indoor humidity is the root cause. The fix is straightforward once you identify which of the seven common causes is at play.

Before we walk through every cause and fix, here are the 3 things you need to know:

  1. Condensation forms when a surface temperature drops below the dew point of the surrounding air
  2. At 75°F and 50% relative humidity, the dew point is approximately 55°F — right at the typical supply air temperature
  3. Occasional light moisture is cosmetic; persistent dripping means something needs to be fixed

Let's start with the physics.


Why Do AC Vents Sweat? The Physics of Vent Condensation

The mechanism is simple. Your air conditioner cools air by passing it over an evaporator coil, which brings the supply air temperature down to approximately 55–60°F. That cold air travels through your ductwork and exits through the supply vents in each room.

The metal grille or register at the end of that duct gets cold — often close to the supply air temperature itself. Meanwhile, the room air surrounding that vent contains water vapor.

If the vent surface temperature drops below the dew point of the room air, the water vapor touching the vent can no longer remain as a gas. It condenses into liquid water — the droplets you see on the grille.

Cold Surface + Humid Air = Water Droplets (Dew Point Explained)

The dew point is the temperature at which air becomes fully saturated and water vapor begins to condense. The more moisture in the air, the higher the dew point — and the easier it is for condensation to form on a cold surface.

According to building science expert Allison Bailes at Energy Vanguard, the critical diagnostic number is 55°F. At the indoor conditions recommended by the Air Conditioning Contractors of America (ACCA) — 75°F and 50% relative humidity — the dew point is approximately 55°F. Since supply air off the evaporator coil typically comes out at 55–60°F, you're operating right at the boundary.

Raise the humidity even slightly — say to 60% RH — and the dew point jumps to approximately 60°F. Now any vent surface at or below 60°F will sweat. That's well within the normal range of supply air temperatures.

This is why the indoor humidity level in your home is the single biggest factor in vent condensation.

Dew Point Reference Table: When Condensation Forms on AC Vents

This table shows the dew point at various indoor temperature and humidity combinations. If the dew point exceeds 55°F, condensation on supply vents becomes likely.

Indoor Temp (°F)Relative HumidityApproximate Dew Point (°F)Will a 55°F Vent Sweat?
7540%~48°FNo
7545%~51°FNo
7550%~55°FBorderline
7555%~57°FYes
7560%~60°FYes — moderate
7565%~62°FYes — heavy
7845%~54°FNo
7850%~57°FYes
7255%~55°FBorderline
7260%~58°FYes
8050%~59°FYes
6863%~55°FBorderline

Use our Dew Point Calculator to check your exact conditions. You'll need a $10–$30 digital hygrometer to measure your indoor temperature and relative humidity.


Occasional vs. Persistent Condensation — When Should You Worry?

Not all vent condensation is a problem. The key distinction is how often it happens and how much water you're seeing.

Normal Condensation (Cosmetic Only)

Light moisture that appears on vents during the most humid days of summer — and dries on its own — is usually nothing to worry about. The same applies to condensation that appears briefly when you first start the AC after a period of inactivity.

The system is cooling down, the vents are cold, and the house is still humid. Give it an hour or two.

Condensation on bathroom vents after a hot shower is also normal. The shower raised the room's humidity well above 60% RH, so the dew point temporarily exceeds the vent temperature. Running the bathroom exhaust fan during and for 20–30 minutes after showering resolves this.

Problem Condensation (Needs Attention)

If water is dripping from your vents daily, water stains are forming on the ceiling around registers, or you notice moisture every time the AC runs — that's persistent condensation. Something is keeping the conditions favorable for continuous moisture formation, and it will get worse if ignored.

Persistent condensation can soak ceiling drywall, degrade insulation R-value, and create the conditions for mold growth.

Mold Risk From Persistent AC Vent Condensation

The EPA is unambiguous: indoor relative humidity should be kept below 60% — ideally between 30% and 50% — to prevent mold growth. Any wet surface that isn't dried within 24–48 hours can begin supporting mold.

The EPA's Mold Course specifically identifies condensation on uninsulated AC ductwork as a moisture problem, and the recommended fix is to insulate the duct on the outside. OSHA recommends preventing condensation by insulating cold surfaces and reducing indoor humidity.

If you see dark spots or detect a musty smell around your AC vents, address it immediately. Mold in HVAC systems can spread spores throughout the entire house via the ductwork.


7 Causes of Condensation on AC Vents (Most Common to Least)

We've ordered these from the cause you should check first to the least likely scenario. For each one: what you'll notice, why it causes condensation, and how to fix it.

1. High Indoor Humidity (Above 55–60% RH)

What you'll notice: Condensation on most or all supply vents throughout the house. Windows may fog up. The house feels muggy even though the thermostat says it's cool.

Why it causes condensation: When indoor humidity rises above 55–60% RH, the dew point of your room air climbs above the surface temperature of your AC vents. At 75°F and 60% RH, the dew point hits 60°F — well above the typical 55°F supply vent temperature. Water condenses on every cold surface in the house.

How to fix it:

  1. Measure your humidity with a digital hygrometer ($10–$30 at any hardware store)
  2. Run a dehumidifier to bring indoor RH down to 45–50% — see our basement dehumidifier settings guide for sizing
  3. Run bathroom and kitchen exhaust fans during and after cooking, showering, and dishwashing
  4. Check that your AC is dehumidifying properlydoes your AC remove humidity? If not, see our AC not removing humidity troubleshooting guide
  5. Keep doors and windows closed while the AC is running — outdoor summer air in the southeastern U.S. regularly carries dew points above 70°F

DIY or Pro? Fully DIY. This is the most common cause and the easiest to fix.

2. Uninsulated or Poorly Insulated Ductwork in Unconditioned Spaces

What you'll notice: Water stains on the ceiling near vent locations. Wet insulation in the attic. Ducts that feel wet or dripping when you inspect them in the attic, crawlspace, or basement.

Why it causes condensation: Supply ducts carry 55–60°F air. In an unconditioned attic that can reach 120°F+ in summer, the temperature difference between the duct surface and the surrounding air is enormous. The hot, humid attic air touches the cold duct surface and immediately hits its dew point. Water drips off the duct, soaks the ceiling insulation, and eventually stains or damages the drywall.

The 2018 IRC (Section N1103.3.1) requires a minimum of R-8 insulation on supply and return ducts 3 inches or larger in attics, and R-6 for ducts in other unconditioned spaces such as crawlspaces and basements. For an overview of what those R-values mean, check our insulation R-value chart.

Duct LocationDuct SizeMinimum R-Value (2018 IRC)
Attic≥3" diameterR-8
Attic<3" diameterR-6
Crawlspace / basement / garage≥3" diameterR-6
Crawlspace / basement / garage<3" diameterR-4.2
Inside conditioned spaceAnyNone required

How to fix it:

  1. Inspect ductwork in the attic, crawlspace, or basement for missing, damaged, or compressed insulation
  2. Re-insulate ducts with foil-faced fiberglass duct wrap rated to at least R-6 (R-8 for attics)
  3. Ensure insulation has a vapor barrier on the warm side (facing outward in summer) to prevent moisture migration through the insulation itself
  4. Separate stacked ducts — one duct laying on top of another compresses insulation and creates condensation hot spots

DIY or Pro? Pro recommended. Attic ductwork is difficult and dangerous to access. Improper insulation installation can trap moisture instead of preventing it.

3. Air Leaks Around the Vent Boot

What you'll notice: Condensation concentrated specifically around the edges of the ceiling register rather than on the grille face. A ring-shaped water stain on the ceiling surrounding the vent. You may feel a slight draft or temperature difference near the vent edges.

Why it causes condensation: The vent boot is the sheet metal box that connects the duct to the ceiling (or floor) opening. If the gap between the boot and the drywall isn't sealed, hot humid air from the attic or crawlspace seeps through that gap and contacts the cold boot surface. Condensation forms at the junction — exactly where those telltale ring-shaped ceiling stains appear.

HVAC professionals on industry forums report this as one of the most commonly overlooked sources of vent condensation. One technician reported recovering 250 CFM of leakage just from sealing boot-to-drywall gaps. Another homeowner saw indoor humidity drop 6–7% after sealing all ceiling vent boots.

How to fix it:

  1. Remove the register grille (usually held by two screws)
  2. Inspect the gap between the sheet metal boot and the surrounding drywall or subfloor
  3. Seal with mastic sealant (water-based, applied with a brush — the industry gold standard) or UL 181-rated foil tape
  4. From the attic side (if accessible), apply mastic to all boot seams and wrap boots with insulated duct wrap sealed with foil tape
  5. Never use standard duct tape — it delaminates within weeks and is not code-compliant for duct sealing
Sealing MethodBest UseDurability
Mastic sealant (water-based)All joints, boot-to-drywall gapsPermanent
UL 181-rated foil tapeClean, smooth metal surfacesLong-lasting
Caulk / siliconeBoot-to-drywall seal (from inside room)Good
Spray foamLarge gaps (>¼") around penetrationsGood
Standard duct tapeNever useFails within weeks

DIY or Pro? DIY from inside the room (remove register, seal with caulk or mastic). Pro recommended for attic-side sealing.

4. Thermostat Set Too Low

What you'll notice: Condensation on most or all vents. The house is very cold — often 68°F or below. Supply air feels ice-cold at the registers.

Why it causes condensation: AC systems typically deliver air that is 18–22°F colder than the return air entering the system. If you set the thermostat to 68°F, the return air is around 68°F, and the supply air may come out at 46–50°F. That supply air temperature is below the dew point in almost any occupied home.

At 68°F and 55% RH, the dew point is approximately 52°F. Supply air at 46°F is well below that — guaranteed condensation.

The ideal AC temperature for balancing comfort and efficiency is typically 72–78°F. Setting it higher narrows the temperature gap between supply air and room air, reducing the condensation risk.

How to fix it:

  1. Raise the thermostat by 2–3°F — going from 68°F to 72°F can eliminate vent condensation entirely
  2. Check the temperature split across your system: measure supply air temperature at a vent and return air temperature at the return grille — the difference should be 18–22°F, not 25°F+

DIY or Pro? Fully DIY.

5. Oversized AC System

What you'll notice: The AC runs in short bursts — less than 10 minutes per cycle — then shuts off. The house reaches temperature quickly but feels clammy and humid. Condensation appears on vents despite the thermostat being set at a reasonable temperature.

Why it causes condensation: An oversized AC produces very cold supply air and short-cycles — meaning it shuts off before the evaporator coil has run long enough to remove humidity. The ACCA Manual J load calculation standard exists specifically to prevent this. According to the Department of Energy, approximately 50% of HVAC systems are incorrectly sized, and oversizing can increase energy consumption by 15–30%.

The result is a double problem for condensation: the supply air is excessively cold (lowering vent surface temperature), and the indoor humidity stays high because the system never runs long enough to dehumidify. Both factors push the dew point above the vent surface temperature.

A properly sized system should run 10–20 minutes per cycle under normal cooling conditions. If your system is cycling every 5–8 minutes, it's likely oversized.

How to fix it:

  1. Time your AC cycles — runs under 10 minutes on a hot day indicate oversizing
  2. Have a Manual J load calculation performed before your next system replacement — this is the ACCA- and DOE-recommended sizing method
  3. Consider a variable-speed or two-stage system at replacement, which can modulate capacity to match actual load
  4. In the meantime, a whole-home dehumidifier can compensate for the humidity the oversized AC fails to remove

DIY or Pro? Pro only. System replacement is the long-term fix. Use our AC tonnage calculator to estimate your home's actual cooling load.

6. Blocked Return Air or Negative Pressure

What you'll notice: Certain rooms sweat more than others. Interior doors whistle or pull shut when the AC is running. Uneven cooling throughout the house.

Why it causes condensation: When return airflow is restricted — by a dirty air filter, closed interior doors, blocked return air vents, or undersized return ductwork — the system creates negative pressure in the house. That negative pressure pulls unconditioned outdoor air (and its high humidity) through every gap: around vent boots, through recessed light fixtures, around plumbing penetrations, and through the building envelope.

That humid infiltration air contacts cold duct surfaces and cold supply vents, causing localized condensation — often worse in rooms farthest from the return.

How to fix it:

  1. Check your air filter — replace it if it's dirty or clogged (this should be the first thing you check anytime your AC isn't performing well)
  2. Keep interior doors open when the AC is running, or install transfer grilles / jumper ducts for closed rooms
  3. Ensure all return vents are unblocked — don't place furniture over return grilles
  4. Have a contractor evaluate return duct sizing — for every ton of AC capacity, you need approximately 400 CFM of airflow, and the return ductwork must accommodate that volume

DIY or Pro? Start DIY (filter, doors, unblock returns). Pro for duct redesign.

7. Poor Ventilation in a Tight House

What you'll notice: Indoor humidity builds steadily through the day, especially in newer construction or recently weatherized homes. Showering, cooking, and even breathing add moisture that has nowhere to go.

Why it causes condensation: Modern energy-efficient homes are tightly sealed — which is great for energy savings but can trap moisture indoors. Without adequate mechanical ventilation, cooking, bathing, laundry, and even occupant respiration raise the indoor humidity and dew point over time.

The EPA notes that tightly sealed buildings may need dedicated exhaust fans or mechanical ventilation to prevent moisture buildup. ASHRAE Standard 62.2 specifies minimum ventilation rates for residential buildings to address this exact problem.

How to fix it:

  1. Run kitchen and bath exhaust fans during all moisture-generating activities
  2. Verify that exhaust fans actually vent to the outside — many are ducted into the attic, which defeats the purpose
  3. Consider installing an ERV (Energy Recovery Ventilator) or HRV (Heat Recovery Ventilator) to bring in fresh, drier outdoor air while recovering energy
  4. Use a standalone dehumidifier as a stopgap

DIY or Pro? DIY for exhaust fan use. Pro for ERV/HRV installation.


How to Stop Condensation on AC Vents: Immediate Fixes

If your vents are sweating right now, here's what to do today — before addressing the root cause.

Lower Indoor Humidity With a Dehumidifier

The fastest way to stop vent condensation is to get the indoor relative humidity below 50%. A portable dehumidifier rated for your room size (or a whole-home unit tied to your HVAC system) will bring the dew point down below the vent surface temperature. See our basement dehumidifier settings guide for sizing recommendations.

Raise the Thermostat 2–3°F

Bumping the thermostat from 70°F to 73°F raises the return air temperature, which warms the supply air by the same amount. That small increase can push the vent surface temperature above the dew point — eliminating condensation without significantly affecting comfort.

Check and Replace Your Air Filter

A clogged filter restricts airflow, which causes the evaporator coil to run colder than normal and drops supply air temperature below design conditions. It also creates the negative-pressure problem that pulls in humid outdoor air. Replace the filter now — this is free and takes 60 seconds.

Run Bathroom and Kitchen Exhaust Fans

These fans remove moisture at the source. Run them during cooking, showering, and dishwashing — and leave them on for 20–30 minutes afterward. Verify they vent to the outdoors and not into the attic.


Long-Term Solutions for AC Vent Condensation

If the immediate fixes reduce but don't eliminate the problem, these structural improvements address the root causes.

Insulate Ductwork in Unconditioned Spaces (R-8 Minimum for Attics)

This is the most impactful long-term fix for homes with ductwork in attics, crawlspaces, or garages. Proper insulation keeps the outer duct surface warm enough to stay above the dew point of the surrounding unconditioned air.

Follow the 2018 IRC minimums: R-8 for attic ducts and R-6 for ducts in other unconditioned spaces. Use foil-faced fiberglass duct wrap with the vapor barrier facing outward (toward the warm air). Our insulation R-value chart covers material options and performance by thickness.

For duct sizing context that affects temperature delivery to each room, see our CFM and duct sizing guide.

Seal Vent Boots With Mastic or Foil Tape

Sealing the connection between the duct boot and the ceiling/floor opening is one of the highest-impact, lowest-cost fixes for vent condensation. Mastic sealant applied with a brush is the most durable option. UL 181-rated foil tape is the acceptable alternative.

Never use standard duct tape.

From inside the room: remove the register, apply caulk or mastic around the gap between the boot and the drywall. From the attic: apply mastic to all boot seams and wrap with insulated duct wrap.

Address an Oversized AC System

If your system is short-cycling and leaving the house humid, the long-term solution is proper sizing at replacement. Insist on a Manual J load calculation — not a rule-of-thumb estimate — before any new system is installed. Our AC tonnage calculator can give you a preliminary estimate of your home's cooling requirements.


Condensation on Ductwork vs. Condensation on Vents

These are the same physics in different locations — but they require different fixes.

Why Your Ducts Sweat in the Attic, Basement, or Crawl Space

When cold supply ducts (55–60°F surface temperature) pass through unconditioned spaces with high humidity and high temperatures, condensation forms on the exterior of the duct. This is invisible from inside the house but causes significant damage: soaked insulation, wet ceiling drywall, water stains, and mold growth in hidden cavities.

The Building Performance Group notes that sweating ductwork can decrease insulation R-value (wet insulation loses its thermal resistance), create moisture damage to ceilings and walls, and feed mold growth that compromises indoor air quality.

How to Stop Ductwork From Sweating

  1. Insulate all ducts in unconditioned spaces to the IRC-required R-values
  2. Seal all duct joints and seams with mastic or UL 181-rated tape to prevent air leakage
  3. Address humidity sources in the crawlspace (install vapor barrier on dirt floors, close foundation vents) or attic
  4. Separate stacked ducts that compress each other's insulation
  5. Consider a supplemental dehumidifier for persistently humid crawlspaces or basements

Why Is My Ceiling Vent Dripping Water?

Ceiling vents are the most common location for visible vent condensation because they're the most exposed to warm room air rising from below (warm air rises and accumulates at the ceiling). The temperature contrast between the cold metal vent and the warm ceiling-level air maximizes the condensation potential.

If you see water dripping specifically from one ceiling vent while others are dry, check for:

  1. An air leak around that specific vent boot — the gap may be larger or more exposed to unconditioned air than other boots
  2. Missing insulation on the duct run feeding that vent — even a short section of uninsulated duct can generate significant condensation
  3. A duct run through a particularly hot section of the attic — ducts near the ridge line get the hottest
  4. A clogged or overflowing drip pan — if condensation from the AC unit itself is overflowing, water can travel through the ductwork. See our guide on AC drip pan overflowing for that specific issue

If water comes from the vent only when it rains, the problem may be a roof leak rather than condensation. Check the roof above that vent location. For window AC units specifically, see our guide on window AC leaking water.


Condensation on AC Vents in Bathrooms — A Special Case

Bathrooms are the #1 room for AC vent condensation because they combine two condensation triggers: very high humidity (from showering and bathing) and a cold supply vent delivering 55–60°F air into that humid space.

At typical post-shower conditions — 80°F+ air temperature and 70%+ RH — the dew point can exceed 70°F. Every cold surface in the room will condense moisture, including the AC vent, mirrors, toilet tank, and cold water pipes.

The fix is exhaust ventilation, not adjusting the AC. Run the bathroom exhaust fan during the entire shower and for at least 20–30 minutes afterward to remove the moisture at its source. If condensation persists, the exhaust fan may be undersized, not ducted to the outside, or not functioning properly.


Water Stains Around AC Vents — Is It Condensation Damage?

Brown or yellowish rings around ceiling registers are almost always caused by condensation. The water runs along the cold vent boot, wicks into the surrounding drywall, and deposits dissolved minerals and dust as it dries — leaving visible stains.

Painting over the stains without fixing the condensation source is a temporary cosmetic fix. The stains will return.

To fix the stains permanently:

  1. Eliminate the condensation source (seal the vent boot, insulate the duct, or lower indoor humidity)
  2. Let the area dry completely for at least 48 hours
  3. Apply a stain-blocking primer (like Kilz or Zinsser) before repainting
  4. Repaint with a mildew-resistant paint for bathrooms and high-humidity areas

Cause Diagnostic Table: Quick Reference

SymptomMost Likely CauseFirst Fix
All vents sweating, house feels muggyHigh indoor humidityRun dehumidifier, check hygrometer
Water stains in ring around ceiling ventAir leak at vent bootSeal boot with mastic or caulk
Ducts dripping in attic/crawlspaceUninsulated ductworkInsulate to R-8 (attic) / R-6 (crawlspace)
Condensation only after showerBathroom humidity spikeRun exhaust fan 20–30 min after shower
All vents condensing, thermostat at 68°FThermostat set too lowRaise to 72–75°F
AC runs 5–8 min cycles, house is humidOversized AC systemHave Manual J calculation done
Condensation worse in certain roomsBlocked returns / negative pressureReplace filter, open doors, unblock returns
New/renovated house, humidity climbs all dayPoor ventilationRun exhaust fans; consider ERV/HRV
Water from vent only when it rainsNot condensation — roof leakInspect roof above vent location

Frequently Asked Questions (FAQ)

Is Water Dripping From My AC Vent Dangerous?

Water dripping from an AC vent is not immediately dangerous, but it shouldn't be ignored. The water itself is clean condensation — not refrigerant or sewage.

However, persistent moisture creates conditions for mold growth. The EPA recommends drying any wet surface within 24–48 hours to prevent mold. Water-damaged drywall can also lose structural integrity over time.

Why Are My AC Vents Only Sweating in Summer?

Summer is when outdoor dew points are highest — often 65–75°F in humid climates. That moisture enters your home through open doors, infiltration, cooking, and bathing.

At the same time, your AC is producing its coldest supply air. The combination of high indoor humidity and cold vent surfaces creates the perfect condensation conditions. In winter, the air is much drier, so dew points are low and condensation on cooling surfaces isn't an issue.

Can Condensation on AC Vents Cause Mold?

Yes. The EPA's Mold Course explicitly identifies condensation on HVAC components as a moisture source that can lead to mold growth. Indoor RH above 60% promotes mold.

If you see dark spots or detect a musty odor near your vents, have the area inspected. Mold remediation for HVAC systems typically costs $1,500–$2,500.

Will a Dehumidifier Stop Condensation on My Vents?

In most cases, yes. If high indoor humidity is the root cause — and it usually is — a dehumidifier that brings RH down to 45–50% will lower the dew point below the vent surface temperature, eliminating condensation.

A portable unit works for individual rooms. A whole-home dehumidifier integrated with your HVAC system is the most effective long-term solution for persistent problems. See our basement dehumidifier settings guide for sizing.

Why Is Only One AC Vent Dripping Water?

If a single vent drips while others stay dry, the problem is localized to that vent — not a whole-house humidity issue. The most likely causes are an unsealed vent boot allowing attic air infiltration at that specific location, missing or damaged insulation on the duct run feeding that vent, or the duct passing through an especially hot part of the attic.

Remove the register and inspect the boot for gaps. Check the attic above that vent for insulation problems.

Should I Close the Vent That Has Condensation?

No. Closing a supply vent doesn't stop condensation — it makes it worse. A closed vent still has cold air behind it, but now the reduced airflow makes the duct even colder. Meanwhile, closing vents increases static pressure in the system, which can worsen negative-pressure infiltration in other parts of the house. The fix is to address the humidity or insulation problem, not restrict airflow.


Sources & References

  1. Energy Vanguard (Allison Bailes) — Why Do Air Conditioning Vents Sweat?
  2. HVAC School — Condensation: It Isn't Where Hot Meets Cold
  3. Greenheck — How to Prevent Condensation in HVAC Grilles, Registers, and Diffusers
  4. U.S. EPA — A Brief Guide to Mold, Moisture and Your Home
  5. U.S. EPA — Mold Course Chapter 2: Moisture and Mold Growth
  6. U.S. EPA — Mold Course Chapter 9: Mold Prevention
  7. U.S. EPA — Main Ways to Control Moisture in Your Home
  8. OSHA — A Brief Guide to Mold in the Workplace
  9. 2018 IRC Section N1103.3.1 — Duct Installation and Insulation (via Knox County)
  10. NJ Energy Code — Duct Systems (2018 IRC/IECC)
  11. Johns Manville — R-12: The New Duct Insulation Standard
  12. Trane — HVAC Condensation: Causes and Solutions
  13. Building Performance Group — Sweating Ductwork Is a Sign of Larger HVAC Issues
  14. Georgia Air Repair (ACCA data) — What Causes Air Conditioner Vents to Sweat?
  15. GreenBuildingAdvisor — Sealing Ducts: What's Better, Tape or Mastic?
  16. Fox Family HVAC — Why Are My AC Registers Sweating?
  17. Wikipedia — Dew Point

If you have any questions about condensation on your AC vents, ductwork sweating, or how to diagnose the specific cause in your home, drop them in the comments below and we'll try to help you out.

This article is part of our Troubleshooting section.